Special Rept 95-02:on 951207,valid failure of 1A EDG identified approx 23 & 1/2 h into 24 h endurance surveillance test.Caused by lubricating oil leak at threaded piping nipple.Threaded nipple replaced. Special Rept 95-02:on 951207,valid failure of 1A EDG identified approx 23 & 1/2 h into 24 h endurance surveillance test.Caused by lubricating oil leak at threaded piping nipple.Threaded nipple replaced.