Jump to main content

LER 96-001-00:on 960110,emergency core cooling pumps declared inoperable due to reduction of ventilation flow. Caused by leak from overhead heating coil that saturated & froze inlet filters.Ice removed.W/960207 ltr. LER 96-001-00:on 960110,emergency core cooling pumps declared inoperable due to reduction of ventilation flow. Caused by leak from overhead heating coil that saturated & froze inlet filters.Ice removed.W/960207 ltr.