LER 96-002-00:on 960514,pressurizer safety valves found to be above Tech Spec setpoint.Caused by setpoint drift.Valves disassembled,inspected,reassembled & reset to proper setpoint.W/960613 ltr. LER 96-002-00:on 960514,pressurizer safety valves found to be above Tech Spec setpoint.Caused by setpoint drift.Valves disassembled,inspected,reassembled & reset to proper setpoint.W/960613 ltr.