LER 93-014-02:on 930722,determine 4 kV vital bus second level undervoltage protection dropout setpoint would not protect motors.Detailed study showed motors would have performed intended safety functions.W/941005 ltr. LER 93-014-02:on 930722,determine 4 kV vital bus second level undervoltage protection dropout setpoint would not protect motors.Detailed study showed motors would have performed intended safety functions.W/941005 ltr.