LER 96-017-00:on 961102,div 3 DG failed to energize emergency bus within required time limit.Caused by personnel misinterpretation of setpoint data.Added note to drawing to clearly show setpoint.W/961127 ltr. LER 96-017-00:on 961102,div 3 DG failed to energize emergency bus within required time limit.Caused by personnel misinterpretation of setpoint data.Added note to drawing to clearly show setpoint.W/961127 ltr.