LER 97-015-00:on 970204,review of design calculations identified min water level in containment sump at time of RSS pumps below vortex suppression grating during LOCA. Caused by inadequate review/process control.Program revised. LER 97-015-00:on 970204,review of design calculations identified min water level in containment sump at time of RSS pumps below vortex suppression grating during LOCA. Caused by inadequate review/process control.Program revised.