LER 97-031-00:on 970507,RHR valve low pressure open permissive bistable setting was set non-conservatively. Caused by implementation of incorrect calibration info. Re-evaluated RHR suction/isolation valve LPI calibrations. LER 97-031-00:on 970507,RHR valve low pressure open permissive bistable setting was set non-conservatively. Caused by implementation of incorrect calibration info. Re-evaluated RHR suction/isolation valve LPI calibrations.