LER 97-003-00:on 970524,manually opened reactor trip occurred due to improper rod bank overlap.Caused by failure of thumbwheel switches due to dirty contacts.Stopped rod motion,cleaned contacts & revised procedure.W/970620 ltr. LER 97-003-00:on 970524,manually opened reactor trip occurred due to improper rod bank overlap.Caused by failure of thumbwheel switches due to dirty contacts.Stopped rod motion,cleaned contacts & revised procedure.W/970620 ltr.