Notice of violation from insp on 970209-0426.Violation noted:during EDG surveillance tests,load test values used were inadequate to ensure that EDGs achieved 2750 kw due to inaccuracies in kilowatt meter instrument loop. Notice of violation from insp on 970209-0426.Violation noted:during EDG surveillance tests,load test values used were inadequate to ensure that EDGs achieved 2750 kw due to inaccuracies in kilowatt meter instrument loop.
Data source
Japan Atomic Energy Agency's Library Catalog
A search system for the collections of the Japan Atomic Energy Agency central library. Books, reports, meeting materials, magazines and dockets collected by the library are searchable.
Last updated
December 31, 2020