Notice of violation from insp on 970209-0426.Violation noted:during EDG surveillance tests,load test values used were inadequate to ensure that EDGs achieved 2750 kw due to inaccuracies in kilowatt meter instrument loop. Notice of violation from insp on 970209-0426.Violation noted:during EDG surveillance tests,load test values used were inadequate to ensure that EDGs achieved 2750 kw due to inaccuracies in kilowatt meter instrument loop.