LER 97-011-00:on 970630,determined that spent fuel pool cooling sys heat removal capability was outside design basis.Caused by siltation of inservice plate-type heat exchanger.Will monitor hydraulic resistance.W/970728 ltr. LER 97-011-00:on 970630,determined that spent fuel pool cooling sys heat removal capability was outside design basis.Caused by siltation of inservice plate-type heat exchanger.Will monitor hydraulic resistance.W/970728 ltr.