LER 97-006-00:on 970828,CR HVAC emergency pressurization unit was found outside TS limits.Caused by TS 4.7.7.1d (1), 4.7.7.1g & 4.7.7.1h being in excess of 800 cfm.Reduced air flow below 800 cfm.W/970926 ltr. LER 97-006-00:on 970828,CR HVAC emergency pressurization unit was found outside TS limits.Caused by TS 4.7.7.1d (1), 4.7.7.1g & 4.7.7.1h being in excess of 800 cfm.Reduced air flow below 800 cfm.W/970926 ltr.