Jump to main content

LER 98-002-01:on 980108,discovered several broken master relay (MR) covers inside SSPS logic cabinet.Caused by past practice of removing MR covers to perform time response testing.Replaced all unnacceptable SSPS MRs.W/980225 ltr. LER 98-002-01:on 980108,discovered several broken master relay (MR) covers inside SSPS logic cabinet.Caused by past practice of removing MR covers to perform time response testing.Replaced all unnacceptable SSPS MRs.W/980225 ltr.