LER 97-013-01:on 971201,torus cooling outboard test valve would not close resulting in inoperable low LPCIS.Caused by faulty breaker auxiliary contact switch.Faulty auxiliary contacts replaced & valve cycled. LER 97-013-01:on 971201,torus cooling outboard test valve would not close resulting in inoperable low LPCIS.Caused by faulty breaker auxiliary contact switch.Faulty auxiliary contacts replaced & valve cycled.