Jump to main content

LER 98-007-00:on 980714,excessive check valve seat leakage in SW supply piping to SFP heat exchangers,occurred.Caused by SW-CV-963 disc sticking in open position.Increased test frequency from quarterly to monthly.W/980813 ltr. LER 98-007-00:on 980714,excessive check valve seat leakage in SW supply piping to SFP heat exchangers,occurred.Caused by SW-CV-963 disc sticking in open position.Increased test frequency from quarterly to monthly.W/980813 ltr.