Notice of violations from insp on 980608-12 & 0715-16. Violations noted:licensee failed to determine lowest voltages available at breaker close & trip coils since original installation of breaker. Notice of violations from insp on 980608-12 & 0715-16. Violations noted:licensee failed to determine lowest voltages available at breaker close & trip coils since original installation of breaker.