LER 98-009-00:on 980915,noted excessive CV,SW-CV-963,seat leakage in SW supply piping to SFP heat exchangers.Caused by subject CV disc being stuck in open position.Valve was exercised & freed from stuck open position.With 981014 ltr. LER 98-009-00:on 980915,noted excessive CV,SW-CV-963,seat leakage in SW supply piping to SFP heat exchangers.Caused by subject CV disc being stuck in open position.Valve was exercised & freed from stuck open position.With 981014 ltr.