LER 98-018-00:on 981006,determined that actual total CRDS flow exceeded indicated CRDS total flow.Caused by degraded CRDS filter bypass valve.Plant has been limited to 1847 MWt & shift check procedure was revised.With 981105 ltr. LER 98-018-00:on 981006,determined that actual total CRDS flow exceeded indicated CRDS total flow.Caused by degraded CRDS filter bypass valve.Plant has been limited to 1847 MWt & shift check procedure was revised.With 981105 ltr.