LER 95-003-00:on 950130,intake structure ventilation sys deficiencies noted.Caused by allowing non-Category 1 exhaust fans to provide cooling for Category 1 SW pump motors.No immediate corrective action taken.W/950227 ltr. LER 95-003-00:on 950130,intake structure ventilation sys deficiencies noted.Caused by allowing non-Category 1 exhaust fans to provide cooling for Category 1 SW pump motors.No immediate corrective action taken.W/950227 ltr.