LER 95-002-00:on 950519,TS LCO 3.1.2.2 & LCO 3.1.2.4 action statements not met.Caused by an unsatisfactory swagelok compression at union of flexible tubing & rigid tubing. Pressure transmitter sensing line repaired.W/950617 ltr. LER 95-002-00:on 950519,TS LCO 3.1.2.2 & LCO 3.1.2.4 action statements not met.Caused by an unsatisfactory swagelok compression at union of flexible tubing & rigid tubing. Pressure transmitter sensing line repaired.W/950617 ltr.