Special rept:on 941006,Unit 1 fuel storage pool conductivity exceeded 10 micro/mho/cm TS limit & returned to within TS on 941010.Caused by decomposition of biological micro-organisms in fuel storage pool.Temporary demineralizer restarted. Special rept:on 941006,Unit 1 fuel storage pool conductivity exceeded 10 micro/mho/cm TS limit & returned to within TS on 941010.Caused by decomposition of biological micro-organisms in fuel storage pool.Temporary demineralizer restarted.