LER 93-002-02:on 930121,Type B & C primary containment local leak rate testing limit exceeded due to leakage past head cooling inlet isolation valve 2-205-2-4.Repaired actuator & verified closing force within specified range.W/941121 ltr. LER 93-002-02:on 930121,Type B & C primary containment local leak rate testing limit exceeded due to leakage past head cooling inlet isolation valve 2-205-2-4.Repaired actuator & verified closing force within specified range.W/941121 ltr.