Special rept:on 950806 & 7,two failures of EDG 1-2 to achieve rated output frequency within TS time limits due to degraded electronic governor performance.Motor-operated potentiometer & electronic governor replaced. Special rept:on 950806 & 7,two failures of EDG 1-2 to achieve rated output frequency within TS time limits due to degraded electronic governor performance.Motor-operated potentiometer & electronic governor replaced.