Interim special rept:on 950816,EDG failed to start during monthly operability surveillance due to failure of Div II starting air block & vent valve.Forward block & vent valve replaced & surveillance test successfully completed. Interim special rept:on 950816,EDG failed to start during monthly operability surveillance due to failure of Div II starting air block & vent valve.Forward block & vent valve replaced & surveillance test successfully completed.