Suppl to final deficiency re undetectable failure in SSPS P-4 signal.TVA will revise appropriate procedures to require tests to verify P-4 contact status following automatic reactor trip or any condition requiring opening of RTBs Suppl to final deficiency re undetectable failure in SSPS P-4 signal.TVA will revise appropriate procedures to require tests to verify P-4 contact status following automatic reactor trip or any condition requiring opening of RTBs