LER 95-009-00:on 951113,pressure setpoint drift of MS sys safety relief valves occurred.Caused by corrosion induced bonding between pilot disc seating surfaces.Several modified SRV pilot discs installed.W/951212 ltr. LER 95-009-00:on 951113,pressure setpoint drift of MS sys safety relief valves occurred.Caused by corrosion induced bonding between pilot disc seating surfaces.Several modified SRV pilot discs installed.W/951212 ltr.