LER 95-015-00:on 951215,discovered omission of RWR seal purge flow from reactor heat balance.Caused by inadequacy in original plant design.Restricted plant output to 2434 MWt to maintain more than 1.4 MWt margin.W/960112 ltr. LER 95-015-00:on 951215,discovered omission of RWR seal purge flow from reactor heat balance.Caused by inadequacy in original plant design.Restricted plant output to 2434 MWt to maintain more than 1.4 MWt margin.W/960112 ltr.